ChurchSafety Logo and homepage linkPencil

ChurchSafety Home >> Information Contents

Exit signs

Exit signs are required by the current fire regulations to inform people of the nearest way out of a building. All exit routes need to be clearly marked using signs that comply with the current fire regulations.

Styles

To conform to the regulations, signs need to include a suitable symbol set of symbols, which are used internationally. Signs that only have the words "Exit" or "Fire Exit" without the symbols must be replaced (or an additional sign must be added which includes the symbols).

Exit signs do not need to have any words at all, but including the words "Fire exit" or "Exit" on a sign will help people understand what the sign means if they are not familiar with the symbols. "Exit" should be used for the main entrance, with all other exit routes (that would only usually be used in a fire or emergency) being marked as "Fire exit" to avoid confusion.

There are two signs types currently allowed by UK fire regulations:
All exit signs comply with one of these styles. 

ISO Exit Sign

Style 1: ISO7010
Sometimes called the British Standard format

This style of exit sign sign shows the moving person going through a doorway.

A version is available with an additional flames symbol, which is intended for helthcare establishments only.

European Standard exit sign

Style 2: European Format (92/58/EEC)

The European style of sign is the preferred style. It shows a separate moving person and a door symbol. Note that the person runs into the doorway, with the arrow inbetween.

The moving person without the rectangular door symbol does not comply with the regulations.

You can presently use either sign style, but only one style of signs should be used to avoid confusion.

Position of signs in rooms

All areas of your Church or Place of Worship need to have fire exit signs installed, especially areas that are used by the public or if there could be confusion as to which doors are exits. You do not need signs if the exit is immediately obvious, such as in the smallest of rooms and spaces.

To start with, place a sign over every 'final exit' door like the main entrance or a fire exit door.  These signs would normally not have an arrow, but could include words to prevent confusion.

Place signs over every exit door in each main room in the building.  There is no need to put signs in small rooms like toilets and offices where there is only one exit and in areas where the public are not normally admitted and the exit route is obvious.  These signs should have a down arrow (or optionally an up arrow for the British Standard sign type, which means 'straight on').

Signs must not be too high and need to be clearly seen in the room.  It is normal practice to fit them just above the exit door, at a height between 2.0 and 2.5 metres from the floor.  Signs can be fitted onto walls by screws or self-adhesive fixings. In some cases, it might be necessary to suspend exit signs on chains so that they can be seen easily or to protect historic building features.

In some situations, signs may be fitted onto doors, but this should be avoided because the sign might be hidden by the open door itself, or people passing through the door.

Position of signs elsewhere

Other signs might be needed to tell people that they need to change direction or move along, for example, a corridor or other space. In these cases, a sign with a directional arrow (left or right) needs to be used. On long corridors, it is a good idea to place exit signs at eye level at regular intervals along the length of the corridor. 

At stairs, it would be usual to use a sign with a 45 degree arrow (such as a down and right arrow).  Signs mounted on walls would usually be fitted below 2.0 metres, but no lower than 1.7 metres.

In some situations, signs are also needed outside of a building, especially if the people evacuating the premises could remain at risk if they remain close to the final exit door.

Some Tips

To prevent confusion, signs should ideally be of a consistent size, shape and style and mounted in similar heights and locations throughout a building.

t is a useful check to make sure that you can always see the next exit sign from any point as you move along the exit route.  This is to ensure that any person who is not familiar with the building has the reassurance of seeing an exit sign from wherever they happen to be.

Keep clear signs

It is essential that fire exit doors are not blocked and are kept clear at all times both inside and out. It is common to use a sign on the outside of fire exit doors to remind people of the need to keep the area clear. The sign would usually be a "mandatory" sign (a blue circle) and would typically read "Fire exit keep clear". Please see our Signs page for more information on safety signs.

Some signs are available that include both the exit sign and a keep clear sign in two sections: one green (the exit sign) and one blue (the keep clear sign).  These can be used on the inside of the door but should not be used on the outside of a building.

[Home Page] [About Us] [Site Map & Search] [FAQ]